Design:

Applicationes:
● Substitutio filis humus existentium et restauratio linearum antiquarum.
● applicabilis ad lineas humili-gradas, ut GJ50/70/90 et etc.
Principalis Features:
● Dimeterium funem parvum, leve pondus, humile onus ad turrim addito;
● Tubus chalybeus in funeri centro collocat, nulla secunda defatigationis mechanica damna.
Repugnantia ad latus pressurae, torsio et distrahens (uno iacuit).
Latin:
ITU-TG.652 | Characteres unius modi fibrorum opticorum. |
ITU-TG.655 | Characteres non-nullae disper- siones unico modo fibrarum opticarum exhibentur. |
EIA/TIA598 B | Col- Codicis fibra retinacula optica. |
IEC 60794-4-10 | Funes optici aerei per lineas potentias electricas-familiae specificationem pro OPGW. |
IEC 60794-1-2 | retinae fibra optica —pars experimenti ratio. |
IEEE1138-2009 | IEEE Standard for testing and performance for optical ground wire for use on electric utilitate lineis virtutis. |
IEC 61232 | Aluminium - Clad filum ferro ad electrica causa. |
IEC60104 | Aluminium magnesium stannum filum pro capite linea conductores. |
IEC 61089 | Filum rotundum concentricis iacebat caput conductores electrica subductis. |
Colorum -12 Chromatographia:

Parameter technicus:
Typical design for Single Layer
Specification | Fibra comitis | Diameter (mm) | Pondus (kg/km) | RTS (KN) | Brevis Circuitus (KA2s) | | |
OPGW-32(40.6; 4.7) | 12 | 7.8 | 243 | 40.6 | 4.7 |
OPGW-42(54.0;8.4) | 24 | 9 | 313 | 54 | 8.4 |
OPGW-42(43.5;10.6) | 24 | 9 | 284 | 43.5 | 10.6 |
OPGW-54(55.9;17.5) | 36 | 10.2 | 394 | 67.8 | 13.9 |
OPGW-61(73.7;175) | 48 | 10.8 | 438 | 73.7 | 17.5 |
OPGW-61(55.1;24.5) | 48 | 10.8 | 358 | 55.1 | 24.5 |
OPGW-68(80.8; 21.7) | 54 | 11.4 | 485 | 80.8 | 21.7 |
OPGW-75(54.5;41.7) | 60 | 12 | 459 | 63 | 36.3 |
OPGW-76(54.5;41.7) | 60 | 12 | 385 | 54.5 | 41.7 |
Typical design for Double Layer:
Specification | Fibra comitis | Diameter (mm) | Pondus (kg/km) | RTS (KN) | Brevis Circuitus (KA2s) |
OPGW-96 (121.7; 42.2) | 12 | 13 | 671 | 121.7 | 42.2 |
OPGW-127 (141.0; 87.9) | 24 | 15 | 825 | 141 | 87.9 |
OPGW-127(77.8; 128.0) | 24 | 15 | 547 | 77.8 | 128 |
OPGW-145(121.0;132.2) | 28 | 16 | 857 | 121 | 132.2 |
OPGW-163 (138.2; 183.6) | 36 | 17 | 910 | 138.2 | 186.3 |
OPGW-163(99.9; 213.7) | 36 | 17 | 694 | 99.9 | 213.7 |
OPGW-183 (109.7; 268.7) | 48 | 18 | 775 | 109.7 | 268.7 |
OPGW-183 (118.4; 261.6) | 48 | 18 | 895 | 118.4 | 261.6 |
Ariovisto:
Detail requisita nobis mittenda pro cable consilio et pretio calculi. Infra requisita debent esse;
A, Power transmission line voltage level
B, fibra comitis
C, Cable structure drawing & diameter
D, Tensile robur
F, Brevis ambitus capacitatis
Typus test
Typus test remitti potest per testimonium factoris exhibendo productum simile factorum in internationali agnito independens organizatio vel laboratorium. Si genus testium praestari debet, fiet secundum processum testium extra genus pacti inter emptorem et opificem ventum.
DEFUNCTORIUS
Optica attenuatio coefficiens in omnibus longitudinum productionibus funiculi mensuratur secundum IEC 60793-1-CIC (ars sparsa, OTDR). Vexillum fibrarum unius-modus ad 1310nm et ad 1550nm metiuntur. Fibrae non-nullae ad 1550nm motatae dispersionis simplicis modus (NZDS) mensurantur.
Factory test
Factory acceptatio probatio duobus exemplis per ordinem peragitur coram emptore vel eius vicario. Requisita qualitatum qualitatum sunt ex signis pertinentibus et pactis qualitatibus consiliis determinantur.
Quality Control - Test Equipment and Standard:
Feedback:Ut signa summae notae mundi occurrant, continuo monitores feedback ex nostris clientibus. Pro commenta et suggestiones, quaeso, contact nos, electronicae:[inscriptio protected].